6.1.1.5
Cable and fuse sizes, NX_6, FR6 to FR9
The table below shows typical cable sizes and types that can be used with the converter. The final
selection should be made according to local regulations, cable installation conditions and cable
specification.
Frame
FR6
NX0004 6—0007 6
NX0010 6—0013 6
NX0018 6
NX0022 6
NX0027 6–0034 6
FR7
NX0041 6
NX0052 6
FR8
NX0062—0080 6
NX0100 6
FR9
NX0125—NX0144 6
NX0170 6
NX0208 6
Table 6-3. Cable and fuse sizes for NX_6 (FR6 to FR9)
1)
based on correction factor 0.7
See chapter 1.3.
CABLING AND CONNECTIONS
I
L
Type
[A]
3—7
10-13
18
22
27-34
41
52
62–80
100
125-144
170
208
Mains and
Fuse
motor cable
[A]
2
Cu [mm
]
10
3*2.5+2.5
16
3*2.5+2.5
20
3*4+4
25
3*6+6
35
3*10+10
50
3*10+10
63
3*16+16
80
3*25+16
100
3*35+16
160
3*95+50
200
250
3*150+70
45(110)
Terminal cable size
Main terminal
Earth terminal
2
[mm
]
[mm
2.5—50 Cu
2.5—35
6—50 Al
2.5—50 Cu
2.5—35
6—50 Al
2.5—50 Cu
2.5—35
6—50 Al
2.5—50 Cu
2.5—35
6—50 Al
2.5—50 Cu
2.5—35
6—50 Al
2.5—50 Cu
6—50
6—50 Al
2.5—50 Cu
6—50
6—50 Al
25—95 Cu/Al
25—95
95-185 Cu/Al2
5—95
6
2
]