C300 Controller installation

To install a C300 Controller

details.
Parts include:
the C300 Controller assembly (control module with IOTA board and mounting
hardware)
2 STP Cat5 Ethernet cables (one Yellow cable, one Green cable)
2 or 4 IOLink cable assemblies for connecting on-board IO Link interface if the
controller is supporting Series C I/O or Process Manager IO modules.
Ensure the cabinet enclosure is connected to a protective earth ground using #8
AWG solid copper wire. There should be metal to metal contact between the
grounding bus bar and the enclosure as well as the carrier.
Considerations
When installing a redundant controller pair consisting of a primary and a partner
secondary controller:
The secondary controller should be installed in the same cabinet as the primary
controller.
The secondary controller may be installed on a separate carrier from the primary
controller.
Both the primary and partner secondary controllers must be connected to the
same pair of Control Firewall (CF9) assemblies.
To install a C300 Controller
Step
1
Refer to appropriate site location drawings for the specified controller
installation location, controller Device Index (FTE address) and wiring
diagrams.
2
Select the mounting location on carrier and align mounting holes in IOTA with
screw hole locations on the carrier.
3
Be sure component side of IOTA is facing up. Secure IOTA to carrier using
screws, washers and spacers provided. Insert spacers and washers between
bottom of IOTA and top of carrier.