Controller Redundancy Specifications - Honeywell Experion C300 User Manual

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Controller redundancy specifications

Control processing switchover interruption time
(
RDNSOTIMEMAX)
Initial synchronization time (from sync start to completion)
(
RDNISTIMEMAX)
Maximum elapsed time between commanded switchover and
completion of initial synchronization
Maximum elapsed time between switchover due to power
cycle of the primary and completion of initial synchronization
Maximum OPM control freeze time (
R301.1
11/06
Specification
RDNOPMFRZTIME)
Experion C300 Controller User's Guide
Honeywell
Controller redundancy specifications
'Go-Back to Idle' option
500 milliseconds
200 seconds
300 seconds
300 seconds
20 seconds