Redundancy tab

The Redundancy Tab displays redundancy-related information and allows redundancy
commands to be issued when the C300 FB is opened on the Monitor Tree in Control
Builder. The following table summarizes the parameter data you can monitor and/or
configure on the Redundancy tab of the configuration form for the selected C300 block.
See
Redundancy parameters
Note that the Redundancy tab is exposed only when the Controller is configured as
redundant. The Module is redundant check box (MODISREDUN parameter) is checked
on the
Main tab
R301.1
11/06
Parameter Name
MODISREDUN
SECMODNAME
ALMENBSTATE
GPSENABLE
(Currently not used)
OVERTEMPTHLD
CPULOLM
CPULOLOLM
also for further descriptions of these parameters.
of the C300 block.
Experion C300 Controller User's Guide
Honeywell
C300 Controller Block
User
Configurable
Project only
Controller is part of
redundant pair
Project only
System assigned name
based on tag name with
sec suffix for secondary
block.
Yes
Allows user to set the
alarm reporting function
used when an alarm
condition is detected by
the function block.
Yes
Allows you to select GPS
as TIMESOURCE for time
synchronization.
Yes
Set threshold value for
module's temperature high
alarm.
Yes
Allows user to set CPU
Free Low Capacity alarm
limit in percent.
No
Fixed CPU Free Low Low
Capacity alarm limit in
percent
Redundancy tab
Notes
79