Activate C300 Controller's CEE
Initial activation order guidelines
Icon
(yellow & yellow)
(shadow &
yellow)
Activate C300 Controller's CEE
For the controller to begin executing its control strategy, you must activate the CEEC300
block.
Initial activation order guidelines
Make the initial activation of control strategy components in Control Builder from the
Monitoring tab in the following suggested order to minimize possible bad data generated
alarms.
Order
1
Control environment components such as:
CEEC300
ACE/CEE
2
Process Manager IOMs
3
PMIO I/O Channels
4
Fieldbus contained function blocks
5
Fieldbus device resident blocks
6
Input/Output Modules (IOMs)
7
Control Modules (CMs) and/or Sequential Control Modules (SCMs)
Activating the CEE
Follow the steps in the table below to activate the CEEC300 block.
Step
1
From the Monitoring Tree, right-click the CEE.
172
Represents . . .
Secondary C300 is not synchronized and
partner C300 is visible partner present.
Secondary C300 is not synchronized and
partner C300 is absent or incompatible
Experion C300 Controller User's Guide
Honeywell
Component
Action
C300 Controller
(C300STATE)
Backup Soft Fail
Backup Soft Fail
R301.1
11/06