Load With Contents command

Loading IOMs and CMs
Before you load IOMs, make sure that the I/O Modules are installed and capable of
communicating with the Server, otherwise errors will result. To Load IOMs, you
select the associated CEEC300 block and perform a
load check boxes for any CMs are not checked in the Load Dialog. You can also
load IOMs individually using the Load command; just be sure that the associated
IOLINK block is loaded first.
Load CMs and SCMs after other control strategy components are loaded. To
Load CMs and SCMs, select the associated CEEC300 block and perform a
with
Contents.' Be sure only load check boxes for CMs and SCMs are checked.
See the Control Building Guide for more details about these procedures.
Load With Contents command
When you select "Load with Contents" from the Tools menu, The Load Dialog box
shows the selected component plus any objects, (IOMs, CMs, etc.) that are contained by
the selected component. For example, when a CEEC300 block is selected for loading,
the Load Dialog will list all the objects assigned to (or contained by) that CEE in the
dialog window. You can then select (or deselect) the objects that you want to load.

Reloading components from project

Reload of component configuration may be necessary especially when you make changes
to the component or function block configuration, or after you replace a failed field
device, I/O module or controller. You can use the applicable previous load procedure to
re-load data to components from the Project or Monitor tab. It is good idea to invoke the
following commands through the Controller menu after a reload operation.
Upload
(perform first), and then
Update to Project
Restrictions and conditions for reloading operations
Re-loading parameter data to certain function blocks may incur some restrictions or
conditions with other related blocks. The following table lists conditions to consider
when re-loading previously loaded blocks.
Block to be
Re-Loaded
PMIO IOMs
154
Conditions or Restrictions
The IOM block state must be IDLE to reload a PMIO IOM block from
the Monitor tab.
Experion C300 Controller User's Guide
Honeywell
'Load with
Contents.' Be sure
'Load
R301.1
11/06