Fte Activity Leds; Table 10 Fte Activity Led Indications - Honeywell Experion C300 User Manual

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

C300 faceplate indicators/displays

FTE activity LEDs

Faceplate
Display
IDLE
Application mode with database loaded, all EEs good with
controller in IDLE – CDA present
OK
Application mode with database loaded, all EEs good with
controller in RUN – CDA present
BKUP
Application mode with database loaded, all EEs good,
module is secondary – CDA present
SF
One or more soft fail conditions are present in the C300
See Note 4
Controller. This state is independent of both CEE state
and Redundancy state.
Note 1: (####) – This symbol does not appear on the C300 Controller faceplate display. It
appears on Control Builder and operator (Station) displays representing the C300 Controller to
indicate that the C300 Controller is OFFNET and this data is not available at this time. Controller
will continue to display the existing or changing faceplate display indication per the current
controller state. As a result of communication failure, CDA will return OFFNET as C300 Module
State.
Note 2: The controller is 'lonely' (cables disconnected or network related problem). Startup halts
until controller can obtain an IP address or validate an internally retained IP address.
Note 3: When a non-redundant controller reboots into the FAIL state, it assumes the backup IP
Address.
Note 4: SF indicates an on-line diagnostic soft failure, such as Battery status, Hardware
Watchdog timer timeout, IOLINK failure, etc.
FTE activity LEDs
Each FTE port on the C300, Series C FIM and Ethernet Switch have one status LED. The
bi-color FTE A and B LEDs indicate connectivity (link present) and communication
activity (transmit and/or receive). Table 10 describes the indications of the FTE Status
LEDs.
FTE A and B
LEDs
RED
166
Indicates...

Table 10 FTE Activity LED Indications

Link integrity check failed – No Ethernet signal detected, or cable is not
connected.
Experion C300 Controller User's Guide
Honeywell
Indicates...
C300 Module
State
(PCMSTATE)
CEEIDLE
CEERUN
BACKUP
SOFTFAIL
R301.1
11/06