Honeywell Experion C300 User Manual page 143

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Plain Text
Channel B Silences
Channel B- Edges
Channel B+ Edges
Last Error
Processor Status
Last IOL Command
Secondary Link Interface
Active Receive
Channel
R301.1
11/06
Parameter Name
PRIIFCHNSILB
PRIIFCHNMNB
PRIIFCHNPLB
PRIIFCOMMERR
PRIIFSTS
LASTIOLCMD
SECIFRCVCHN
Experion C300 Controller User's Guide
Honeywell
User
Configurable
No
The number of I/O link
silences on channel B
encountered locally by
the primary link
interface.
No
The number of I/O link
channel B missed
minus edge transitions
encountered locally by
the primary link
interface.
No
the number of I/O link
channel B missed plus
edge transitions
encountered locally by
the primary link
interface.
No
The last I/O link
communications error
experienced by the
primary link interface.
No
The status of the link
processor for the
primary link interface.
No
The last I/O link
command requested
through the COMMAND
parameter or the last
SELECT_CH_A /
SELECT_CH_B
command automatically
issued when periodic
channel swap is
enabled.
No
The channel that is
actively listening to
transmitted messages.
IOLINK Block
Statistics tab
Notes
127

Advertisement

Table of Contents
loading