FTE A and B
LEDs
OFF
Blinking
GREEN

C300 faceplate display indications

The C300 Controller faceplate display rotates through the following fields when
controller is operating from its Application firmware:
<Device Index> -> < Controller State>-> <Redundancy Status>
For example:

Table 11 Display indications when controller is in application mode

Primary
Controller
Device Index
#nnn
Controller
NODB / IDLE
State
/ RUN / OK
Redundancy
-np-
Status
!cpt
!syn
xxx%
sync
R301.1
11/06
Link integrity is OK – Ethernet signal is present, but no activity on link.
Typically, every FTE node should show some activity. If the LED is
observed for several seconds, some activity should be seen.
Link integrity signal is present, with activity on link.
During normal operation the FTE A and B LEDs should be blinking at a
variable rate indicating normal network activity.
Moderate to high network traffic conditions may cause the LEDs to
appear as steady green.
#003 -> RUN -> sync
Secondary
Controller
#nnn
BKUP
-np-
!cpt
!syn
xxx%
sync
Experion C300 Controller User's Guide
Honeywell
C300 faceplate display indications
Indicates...
Description
FTE Device Index, where nnn can be 001 to
510. Does not change with redundancy role.
Implies redundancy role.
No secondary/primary partner.
Non-compatible partner visible
Partner controller visible, but not
synchronized and initial sync not in progress.
Initial sync is in progress, where xxx can be
000 to 100 to indicate percentage complete.
Redundant controller pair is synchronized.