Mounting on a non-metallic container

To install a single lead probe into a non-metallic (plastic) vessel, the probe must be
mounted with a metal flange (>2"/DN50) or if a threaded process connection is in
use, the probe must be screwed into a metal sheet (diameter > 8"/200 mm).
Figure 14
depicts an example of mounting in concrete silos, the placement of the concrete
versus the metal sheet used to secure the transmitter. Both
considered non-metallic mounts. Both types of mountings are subject to the same
specifications as described in Mounting on a non-metallic container.
December 2017

Figure 13: Mounting on a non-metallic vessel

Figure 14: Mounting in concrete silos

Quick Start Installation Guide
Figure 13
and
Figure 14
are
23