Set The Jumpers For Foundation Fieldbus (Ff); Table 9: Foundation Fieldbus Write Protect - Honeywell SLG 700 Quick Start Manual

Smartline level guided wave radar
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Set the Jumpers for FOUNDATION Fieldbus (FF)

There is no Failsafe jumper on the FOUNDATION Fieldbus transmitters, but there
is a Write Protect jumper and a simulation-mode jumper (see manual 34-SL-25-
07).
ATTENTION: Electrostatic Discharge (ESD) hazards. Observe
precautions for handling electrostatic sensitive devices.
Step
Turn OFF Transmitter power.
1
Loosen the end-cap lock, and unscrew the end cap from the
2
Electronics side of the Transmitter housing.
If applicable, carefully depress the tabs on the sides of the Display
Module and pull it off.
3
Set the Write Protect jumper (Bottom jumper) to the desired behavior
(Protected or Unprotected). See
4
Replace the Display Module, if applicable.
5
Screw on the end cap and tighten the end-cap lock.
6
Turn ON Transmitter power.
7
Table 9: FOUNDATION Fieldbus Write Protect and Simulation Mode jumper positions.
Image
Description
Fieldbus SIM Mode = OFF
Write Protect = OFF (Not Protected)
Fieldbus SIM Mode = OFF
Write Protect = ON (Protected)
Fieldbus SIM Mode = ON
Write Protect = OFF (Not Protected)
Fieldbus SIM Mode = ON
Write Protect = ON
Action
Table 9
for jumper positioning.