CHAPTER 6: METERING

Power Demand

Directional Power
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
This menu shows the real, reactive, and apparent power demands along with their
maximums. The maximums can be cleared by resetting them from Records \Clear Records
\Max Real /Reactive /Apparent Demand.
Path:
Metering > Power Demand 1(X)
Reset (Reset Dmd Date/Time) MM/DD/YY 00:00:00
Real Demand (Real Dmd)
Range: 0.0 kW to 214748364.7 kW
Maximum Real Demand (Max Real Dmd)
Range: 0.0 kW to 214748364.7 kW
Date/Time Real Demand (Date/Time Real Dmd) MM/DD/YY 00:00:00
Reactive Demand (Reactive Dmd)
Range: 0.0 kvar to 214748364.7 kvar
Maximum Reactive Demand (Max Reactive Dmd)
Range: 0.0 kvar to 214748364.7 kvar
Date/Time Reactive Demand (Date/Time Reactive Dmd) MM/DD/YY 00:00:00
Apparent Demand (Apparent Dmd)
Range: 0.0 kVA to 214748364.7 kVA
Maximum Apparent Demand (Max Apparent Dmd)
Range: 0.0 kVA to 214748364.7 kVA
Date/Time Apparent Demand (Date/Time Apparent Dmd) MM/DD/YY 00:00:00
Path:
Metering > Directional Power
The effective operating quantities of the sensitive directional power elements are
displayed here. The display may be useful to calibrate the feature by compensating the
angular errors of the CTs and VTs with the use of the RCA and CALIBRATION settings.
Directional Power 1 (Directional Power 1)
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
Directional Power 2 (Directional Power 2)
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
Directional Power X (Directional Power X)
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
POWER DEMAND