SOFTWARE INTERFACE
Transient Recorder
(Waveform Capture)
3–46
The software can be used to capture waveforms (or view trace memory) from the relay at
the instance of a pickup, trip, alarm, or other condition.
With software running and communications established, select the Records >
Transients > Transient Records menu item to open the Transient Recorder Viewer
window.
Click on Trigger Waveform to trigger a waveform capture.
To view the captured waveforms, click on the Launch Viewer button. A detailed
Waveform Capture window appears as shown below.
Click on the Save button to save the selected waveform to the local PC. A new window
appears, requesting the file name and path. One file is saved as a COMTRADE file, with
the extension "CFG." The other file is a "DAT" file, required by the COMTRADE file for
proper display of waveforms.
To view a previously saved COMTRADE file, click the Open button and select the
corresponding COMTRADE file.
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL