Monitoring - GE 869 Instruction Manual

Motor protection system
Hide thumbs Also See for 869:
Table of Contents

Advertisement

MONITORING

Monitoring
Breaker
Trip and Close Circuit
Monitoring
4–262
Figure 4-102: Monitoring Display Hierarchy
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
Testing
Level 1
The 869 relay provides Trip and Close Circuit Monitoring elements.
The first and second Form A relay outputs on slot "F" include a circuit to monitor the DC
voltage across the output contact when it is open. To do that, an external jumper is wired
between the terminals "FA_1 COM" and "FA_1 OPT/V" for the Trip coil monitoring, or/and
"FA_2 COM" and "FA_2 OPT/V" for the Close coil monitoring.
The monitor contains a level detector whose output is set to logic 1 (ON) when the voltage
is above 20 volts. The voltage monitor is used to check the health of the overall trip and
closing circuit.
The two figures below show the two different connections of the breaker trip and close
coils to the relay's trip and close output relays for either no voltage monitoring and for
voltage monitoring of the circuits.
Breaker
Broken Rotor Bar
Stator Inter-Turn Fault
Data Capture
Functions
Data Capture
Harmonic Detection
Speed Protection
Data Capture
RTD Temperature
Data Capture
Data Capture
Loss of Communications
Level 2
Level 3
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS
Trip Circuit Monitoring
Close Circuit Monitoring
Breaker Arcing Current
Breaker Health
Power Factor
Level 5:
Demand
Current
Real Power
Reactive Power
Pulsed Outputs
Apparent Power
Digital Counters
Level 4