CHAPTER 4: SETPOINTS
USB
FASTPATH:
FASTPATH:

Ethernet Ports

869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 4-8: Example of WiFi Deployment
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Mask: 255.255.255.0
IP Gateway: 172.16.0.1
Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in
again for proper communication to be established over USB.
Connecting multiple 8 Series relays over USB to a single PC is not possible because in the
case of USB, the IP address of the device 172.16.0.2 is constant.
The following communication offerings are available.
Base Offering
Modes: 10/100 Mbps
One Port: RJ45
Protocol: Modbus TCP
Communications Card Option "C" - 2x Copper (RJ45) Ports
Modes: 10/100 MB
Two Ports: RJ45 (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEEE 1588, SNTP, IEC
62439-3 clause 4 (PRP)
Communications Card Option "S" - 2x ST Fiber Ports
Modes: 100 MB
Two Ports: ST (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEEE 1588, SNTP, IEC
62439-3 clause 4 (PRP)
Wavelength: 1310 nm
Typical link distance: 4 km
DEVICE
4–31