DEVICE
FASTPATH:
FASTPATH:

IEC 61850

The IEC 61850 Configurator
4–42
IEC103 Sync Timeout
Range: 0 to 1440 minutes in steps of 1 min
Default: 0 min
IEC103 Activity Timeout
Range: 0 to 3600 seconds in steps of 1 s
Default: 0 s
All binary inputs are configured from FlexLogic operands. For a complete list, see Format
Code FC142.
The user must pay attention when configuring the function type and information number
of the different points, because they must be unique. There is no mechanism in the
EnerVista 8 Series Setup software or the front panel HMI to detect duplication of the
information index.
The IEC 60870-5-103 point lists always begin with point 0 and end at the first "Off" value.
Since IEC 60870-5-103 point lists must be in one continuous block, any points assigned
after the first "Off" point are ignored.
The optional communications processor supports both the IEC61850 GOOSE and IEC
61850 MMS Server service as per IEC 61850 standard Ed. 2. The GOOSE messaging service
provides the 869 unit the ability to Publish/Subscribe Digital Input Status and its Quality
and Timestamp to/from other IEDs with supporting GOOSE messaging service, while the
server support allows remote control center, RTU/Gateway, local HMI or other client role
devices access to the relay for monitoring and control. The configuration of IEC61850
services is accomplished using the 869 configuration software, EnerVista 8 Series
Setup software. A rebooting MUST be done before any changes made take affect.
The 869 supports the IEC 61850 protocol which is identified by order code option "2E".
The IEC 61850 configurator is found in both the online and offline section of the EnerVista
8 Series Setup software for configuring the online 869 and offline 869 settings file
respectively.
Online and Offline Setup
ONLINE SETTINGS FILE
Two options are available to configure the relay's online settings file.
1.
Configuration
Configure the 869 (having order code option: IEC 61850) through the Device Setup
or Quick connect screen.
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS