CHAPTER 1: INTRODUCTION

Monitoring

869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TRIP BUS
Number of Elements: ........................................6
Number of Inputs:...............................................16
Pickup Time Delay:.............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay: .........................................0.000 to 6000.000 s in steps of 0.001 s
Operate Time:.......................................................< 2 ms at 60 Hz
Timer Accuracy: ..................................................± 3% of delay time or ± ¼ cycle (whichever is greater) from
BREAKER ARCING CURRENT
Mode:........................................................................3-pole
Principle:..................................................................accumulates breaker duty (I
Initiation: .................................................................any operand
Alarm Threshold: .................................................0 to 50000 kA2-cycle in steps of 1 kA2-cycle
Timer Accuracy: ..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
BREAKER FAILURE
Mode:........................................................................3-pole
Current Supervision: ..........................................phase and neutral current (fundamental phasor magnitude)
Current Supervision Pickup:...........................0.050 to 30.000 x CT in steps of 0.001 x CT
Current Supervision Dropout: .......................97 to 98% of pickup
Current Supervision Accuracy:.....................For 0.1 to 2.0 x CT: ± 0.5% of reading or ± 0.4% of rated
Time Delay:............................................................0.000 to 6000.000 s in steps of 0.001 s
Timer Accuracy: ..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
Reset Time: ............................................................< 10 ms typical at 2 x Pickup at 60 Hz
BREAKER HEALTH
Timer Accuracy: ..................................................± 3% of delay setting or ± 1 cycle (whichever is greater) from
BROKEN ROTOR BAR
Operating Parameter:.......................................Fundamental Phasor Magnitude
Pickup Level:..........................................................-60db to -12db in steps of -1dB
Dropout Level: ......................................................97 to 98% of Pickup
CLOSE CIRCUIT MONITOR (CCM)
Applicable Voltage: ............................................20 to 250 VDC
Trickle Current: .....................................................1 to 2.5 mA
Timing Accuracy:................................................± 3 % or ± 4 ms, whichever is greater
DEMAND
Measured Values:................................................Phase A/B/C present and maximum current
Measurement Type:...........................................Thermal Exponential, 90% response time (programmed): 5,
Current Pickup Level:.........................................10 to 10000 in steps of 1 A
Dropout Level: ......................................................96-98% of Pickup level
Level Accuracy:....................................................± 2%
pickup to operate
2
from pickup to operate
(whichever is greater),
For > 2.0 x CT: ± 1.5% of reading
from pickup to operate
< 12 ms typical at 2 x Pickup at 50 Hz
pickup to operate
10, 15, 20, 30 minutes
Block Interval / Rolling Demand, time interval (programmed):
5, 10, 15, 20, 30 minutes
SPECIFICATIONS
t) during fault
1–21