CHAPTER 3: INTERFACES
Loading Setpoints
from a File
CAUTION:
Uninstalling Files and
Clearing Data
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
An error message occurs when attempting to upload a setpoint file with a revision
number that does not match the relay firmware. If the firmware has been upgraded
since saving the setpoint file, see Upgrading Setpoints Files to a New Revision for
instructions on changing the revision number of a setpoint file.
The following procedure illustrates how to load setpoints from a file. Before loading a
setpoints file, it must first be added to the 869 environment as described in the section,
Adding Setpoints Files to the Environment.
1.
Select the previously saved setpoints file from the File pane of the 869 software main
window.
2.
Select the Offline > Edit Settings File Properties menu item and verify that the
corresponding file is fully compatible with the hardware and firmware version of the
target relay. If the versions are not identical, see Upgrading Setpoint Files to a New
Revision for details on changing the setpoints file version.
3.
Right-click on the selected file and select the Write Settings File to Device item.
4.
Select the target relay from the list of devices shown and click Send. If there is an
incompatibility, an error of the following type occurs:
If there are no incompatibilities between the target device and the settings file, the data is
transferred to the relay. An indication of the percentage completed is shown in the bottom
of the main window.
The unit can be decommissioned by turning off the power to the unit and disconnecting
the wires to it. Files can be cleared after uninstalling the EnerVista software or the relay, for
example to comply with data security regulations. On the computer, settings files can be
identified by the .cid extension.
To clear the current settings file do the following:
1.
Create a default settings file.
2.
Write the default settings file to the relay.
3.
Delete all other files with the .cid extension.
4.
Delete any other data files, which can be in standard formats, such as COMTRADE or
.csv.
You cannot directly erase the flash memory, but all records and settings in that memory
can be deleted. Do this from the front panel or EnerVista software using:
RECORDS > CLEAR RECORDS