Overload Alarm - GE 869 Instruction Manual

Motor protection system
Hide thumbs Also See for 869:
Table of Contents

Advertisement

CHAPTER 4: SETPOINTS

Overload Alarm

869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
The Overload Alarm is used to alarm abnormal load increases that can indicate problems
with the process. An alarm is enabled only after the acceleration stage is complete and the
motor has entered the running or overload stage. Once enabled, the alarm is generated
when the average phase current exceeds the Pickup setting for the time delay specified by
the setting Pickup Delay. When the current has subsided, the alarm stays active for the
time specified by the setting Dropout Delay.
Path:
Setpoints > Protection > Group 1 > Motor > Overload Alarm
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
PICKUP
Range: 0.50 to 3.00 x FLA in steps of 0.01 x FLA
Default: 0.70 x FLA
PICKUP DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
DROPOUT DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
For details see
Common
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
Setpoints.
PROTECTION
4–155

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents