CHAPTER 1: INTRODUCTION

Specifications

Device
Protection
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
To obtain the total operating time, i.e. from the presence of a trip condition to initiation of a
trip, add 8 ms output relay time to the operate times listed below.
ANNUNCIATOR PANEL
Number of Elements: ........................................1 (36 indicators)
Layout:.....................................................................Grid of 2x2 or 3x3
Data Storage:........................................................Non-volatile memory
Mode:........................................................................Self-reset, latched, acknowledgeable
Display Text: ..........................................................3 lines of 15 characters maximum
Visual Indication:.................................................Flashing: 2Hz @ 50% duty cycle
CUSTOM CONFIGURATIONS
Config Mode:.........................................................Simplified, Regular
ACCELERATION TIME (37P)
Acceleration Current: ........................................1.00 to 10.00 x FLA in steps of 0.01
Operating Mode: .................................................Definite Time, Adaptive
Timing Accuracy:................................................±100 ms or ±0.5% of total time (whichever is greater),
ARC FLASH HS PHASE/GROUND INSTANTANEOUS OVERCURRENT HS 50P/50G
Current:....................................................................Phasor Magnitude (special high speed algorithm)
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................For 0.1 to 0.2 x CT: ± 0.2% of reading or 1.5% of rated,
Operate Time:.......................................................4 ms at >6 x Pickup at 60 Hz
AUXILIARY OVERVOLTAGE (59X)
Operating Parameter:.......................................Vx (Phasor)
Pickup Level:..........................................................0.00 to 3.00 x VT in steps of 0.01 x VT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................±0.5% of reading from 10 to 240 V
Overvoltage Curves: ..........................................Definite Time, Inverse Time, FlexCurves A/B/C/D
Pickup Time Delay:.............................................0.000 to 6000.000 s in steps of 0.001s
Dropout Time Delay: .........................................0.000 to 6000.000 s in steps of 0.001s
Pickup Accuracy:.................................................'Auxiliary voltage input channel error
Operate Time:.......................................................< 30 ms at 1.1 x pickup at 60Hz
Curve Timing Accuracy: ..................................at >1.1 x PKP: 3.5% of operate time ± ½ cycle (whichever is
Timer Accuracy: ..................................................± 3% of operate time or ± ½ cycle (whichever is greater)
applicable to definite time mode only
whichever is greater
For > 0.2 x CT: ± 1.5% of reading
5 ms at >6 x Pickup at 50 Hz
4-8 ms at > (3-6) x Pickup at 60 Hz
4-10 ms at > (3-6) x Pickup at 50 Hz
greater) from pickup to operate
SPECIFICATIONS
1–11