SPECIFICATIONS

Outputs

1–28
ARC FLASH SENSOR/FIBER
Number of Point Sensors:............................... 4
Detection Radius: ............................................... 180 degree
Maximum Fiber Length (Point Sensor):..... 18 ft
Fiber Size: ............................................................... 1000 um
Mode:........................................................................ Multi-mode
Connector: ............................................................. Small Media Interface (SMI)
Fiber Type: ............................................................. Plastic Optical Fiber
Bend Radius: ......................................................... >25 mm
CONTACT INPUTS
Number of Inputs: .............................................. Based on relay ordering
Type: ......................................................................... Wet or Dry
Wet Contacts:....................................................... 300 V DC maximum
Selectable thresholds: ...................................... 17, 33, 84, 166 VDC
Tolerance:............................................................... ±20%
Recognition time:................................................ 1 ms (typical)
Debounce time: ................................................... 0.0 to 16.0 ms in steps of 0.5 ms
Continuous current draw (burden): ............ 2 mA
CLOCK
Setup: ....................................................................... Date and Time, Daylight Saving Time, UTC (Coordinated
Backup Retention: .............................................. 1 hour
IRIG-B INPUT
Auto-detect: .......................................................... DC and AM
Amplitude Modulation:..................................... 1 V to 10 V pk-to-pk
DC Shift:................................................................... TTL
Input Impedance: ............................................... 40 kΩ
Isolation: ................................................................. 2 kV
RTD INPUTS
Types (3-wire): ...................................................... 100 Ω Platinum, 120 Ω Nickel, 100 Ω Nickel, 10 Ω Copper
Sensing current: .................................................. 5 mA
Range:...................................................................... –40 to +250°C (-40 to +482°F)
Accuracy: ............................................................... ±2°C (±4°F)
Isolation: ................................................................. 36 V pk-pk (a group of RTDs to ground)
Lead Resistance: ................................................. 25 Ohms max. per lead for platinum or nickel and 3 Ohms
ANALOG OUTPUTS
Range (configurable):........................................ 0 to 1mA, 0 to 5mA, 0 to 10mA, 0 to 20mA, 4 to 20mA
Max. load resistance: ........................................ 10 kΩ @ 1 mA,
Accuracy: ............................................................... ± 1% of full scale
Isolation: ................................................................. 500V DC for one minute (functional isolation between analog
Driving Signal: ...................................................... any Analog quantity
Sampling Interval: .............................................. Typically 500 ms
Upper and lower limit
(for the driving signal): ............................... -90 to 90 pu in steps of 0.001
Universal Time)
max. per lead for copper RTDs
600 Ω @ 20 mA
inputs and output group; and each group of chassis)