GE 869 Instruction Manual page 26

Motor protection system
Hide thumbs Also See for 869:
Table of Contents

Advertisement

SPECIFICATIONS
FASTPATH:
NOTE:
1–16
PHASE/NEUTRAL/GROUND TIME OVERCURRENT (51P/N/G)
Current:.................................................................... Phasor or RMS
Pickup Level: ......................................................... 0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:...................................................... 97 to 98% of Pickup
Level Accuracy: ................................................... For 0.1 to 2.0 x CT: ±0.5% of reading or ±0.4% of rated,
Curve Shape:......................................................... IEEE Extremely/Very/Moderately Inverse;
Curve Multiplier: .................................................. 0.05 to 600.00 in steps of 0.01
Reset Time: ............................................................ Instantaneous, Timed
Curve Timing Accuracy:.................................. Currents > 1.03 to 20 x pickup: ± 3% of operate time or ± ½
Voltage Restrained Function (51V): ............ Modifies Pickup from 0.1 < V < 0.9 VT Nominal in a fixed
Add 1.5 cycles to the curve time to obtain the TOC operating time, i.e., from fault inception
until operation.
PHASE/NEUTRAL/GROUND INSTANTANEOUS OVERCURRENT (50P/N/G)
Current (for Phase IOC only): ......................... Phasor or RMS
Current (for Neutral/Ground IOC only):..... Fundamental Phasor Magnitude
Pickup Level: ......................................................... 0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:...................................................... 97 to 98% of Pickup
Level Accuracy: ................................................... For 0.1 to 2.0 x CT: ±0.5% of reading or ±0.4% of rated,
Operate Time: ...................................................... <12 ms typical at 3 × Pickup at 60 Hz (Phase/Ground IOC)
Operating time specifications given above are applicable when RMS inputs are used.
Typical times are average operate times over multiple test cases.
Timer Accuracy:.................................................. ±3% of delay setting or ± ¼ cycle (whichever is greater) from
PHASE REVERSAL
Phase Reversal Condition:.............................. V
Configuration: ...................................................... ABC or ACB phase rotation
Pickup/Dropout Time Delay: ......................... 0.00 to 180.00 s in steps of 0.01 s
Timer Accuracy:.................................................. ±3% of delay setting or ±1% cycle (whichever is greater)
whichever is greater;
For > 2.0 x CT: ±1.5% of reading
ANSI Extremely/Very/Normally/Moderately Inverse;
Definite Time, IEC A/B/C and Short Inverse;
IAC Extremely/Very/Inverse/Short Inverse;
2
4
FlexCurve A/B/C/D, I
t, I
t
cycle (whichever is greater) from pickup to operate
linear relationship
whichever is greater
For > 2.0 x CT: ±1.5% of reading
<16 ms typical at 3 × Pickup at 60 Hz (Neutral IOC)
<15 ms typical at 3 × Pickup at 50 Hz (Phase/Ground IOC)
<20 ms typical at 3 × Pickup at 50 Hz (Neutral IOC)
pickup to operate
/V
=100% when phase to phase voltages are greater than
2
1
50% of VT
from pickup to operate
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL