Forming circuit for Line Modules
Note
Forming the Line Modules
Voltage must be supplied to Line Modules via a connected Motor Module and the associated
DC link.
Figure 10-21 Forming circuit for Line Modules
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
WARNING
Risk of death from electric shock when installation of lamp sockets is non-insulated
If two incandescent lamps connected in series are used, the insulation of the lamp
sockets is not rated for the high voltage of 500 to 690 V 3 ph AC.
• For a line voltage of 500 to 690 V 3 ph AC, install the two lamp sockets connected in
series with insulation and protect them from being touched.
Maintenance and servicing
10.5 Forming the DC link capacitors
405