Advertisement

Line Modules
5.2 Basic Line Modules
Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130, PT1000 or PTC measuring sensor in the stator windings.
Note
Connection to terminal strip -X9
A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and
-X9:7.
5.2.3.6

X42 terminal strip

Table 5- 5
Max. connectable cross-section: 2.5 mm
Note
Connection options of terminal strip X42
The terminal strip is not intended to generally provide a 24 V DC supply (for example for
supplying additional components on the plant or system side), as the voltage supply of the
Control Interface Module could also be overloaded and the correct functioning could thus be
compromised.
146
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
Function
1
P24L
2
3
M
4
Technical data
Power supply for Control Unit, Sensor Module
and Terminal Module (18 ... 28.8 V)
maximum load current: 3 A
2
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7