Ambient conditions
Degree of protection
Protection class
Touch protection
Cooling method according to
EN 60146-1-1
Cooling circuit
Max. system pressure with respect to
atmosphere
Pressure drop at the heat sink at rated
volumetric flow
Recommended pressure range
Inlet temperature of liquid coolant
Permissible ambient temperature (air) in
operation
Climatic ambient conditions
Storage
2)
Transport
2)
Operation
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
IP00 according to EN 60529 (IP20, without taking into account the connecting
busbars)
Class I (with protective conductor system) and class III (PELV) according to
EN 61800-5-1
EN 50274 and DGUV regulation 3 when used for the intended purpose
Power Modules, Basic Line Modules, Active Line Modules, Motor Modules:
WE
W: Liquid cooling
E: Forced cooling, drive device outside the equipment
Active Interface Modules, air-cooled: AF
A: Air cooling
F: Forced cooling, drive unit inside the device
Active Interface Modules, liquid-cooled: WE
W: Liquid cooling
E: Forced cooling, drive device outside the equipment
Line reactors, sine-wave filters, motor reactors, dv/dt filters with voltage
peak limiter: AN
A: Air cooling
N : Natural cooling (convection)
600 kPa
70 kPa
80 ... 200 kPa
Dependent on ambient temperature, no condensation permitted
0 ... 45 °C without derating, > 45 ... 50 °C see derating characteristics
(temperature range between 0 °C and 5 °C - only with antifreeze; anti-
freeze: Antifrogen N, Antifrogen L and Dowcal 100)
Dependent on inlet temperature of liquid coolant, no condensation permit-
ted:
0 ... 45 °C without derating
> 45 ... 50 °C, refer to derating characteristics
Class 1K4 according to EN 60721-3-1, temperature -25 ... +55 °C
max. Air humidity 95 %
Class 2K4 according to EN 60721-3-2, temperature -25 ... +70 °C,
max. humidity, 95% at +40 °C
better than Class 3K3 according to EN 60721-3-3,
Relative humidity: 5 ... 95 % (no condensation)
Oil mist, salt mist, ice formation, condensation, dripping water, spraying
water, splashing water and water jets are not permitted