NOTICE
Risk of damaging sine-wave filter by exceeding the maximum output frequency
The maximum permissible output frequency when sine-wave filters are used is 150 Hz.
The sine-wave filter can be damaged if the output frequency is exceeded.
• Operate the sine-wave filter with a maximum output frequency of 150 Hz.
NOTICE
Damage to the sine-wave filter if it is not activated during commissioning
The sine-wave filter may be damaged if it is not activated during commissioning.
• Activate the sine-wave filter during commissioning via parameter p0230 = 3.
NOTICE
Damage to the sine-wave filter if a motor is not connected
Sine-wave filters, which are operated without a motor being connected, can be damaged or
destroyed.
• Never operate a sine-wave filter on the Power Module or Motor Module without a
Note
Cable lengths
Keep the connecting cables to the Power Module or Motor Module as short as possible
(max. 5 m).
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
connected motor.
Motor-side power components
7.1 Sine-wave filter