Motor-side power components
7.2 Motor reactors
Table 7- 10
Technical data of motor reactors 500 V ... 690 V 3 AC, Part 2
Article number
Suitable for Motor Module
Type rating of the Motor Module
Rated current
Power loss
- At 50 Hz
- At 150 Hz
Connections
- To the Motor Module (1U1, 1V1, 1W1)
- Load (1U2, 1V2, 1W2)
- PE
Max. permissible cable length between
the motor reactor and motor
- without motor reactor
- for 1 motor reactor
- for 2 motor reactors in series
Degree of protection
Dimensions
Width
Height
Depth
Weight, approx.
256
6SL3000-
2AH34-
7AA0
6SL3325-
1TG34-
7AAx
kW
450
A
465
kW
0.631
kW
0.723
M12
M12
M8
m
m
m
IP00
mm
410
mm
392
mm
292
kg
80
2AH35-
2AH38-
8AA0
1AA0
1TG35-
1TG37-
8AAx
4AAx
1TG38-
0AAx
1TG38-
1AAx
560
710
800
800
575
810
0.705
0.877
0.801
1.003
M12
M12
M12
M12
M8
M8
300 (shielded) / 450 (unshielded)
300 (shielded) / 450 (unshielded)
525 (shielded) / 787 (unshielded)
IP00
IP00
410
410
392
392
292
279
80
146
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
2AH41-
2AH41-
1AA0
3AA0
1TG41-
1TG41-
0AAx
3AAx
1000
1200
1025
1270
0.927
0.862
1.052
0.952
M12
M12
M12
M12
M8
M8
IP00
IP00
410
460
392
392
317
296
163
153