Siemens Sinamics S120 Manual page 190

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Line Modules
5.3 Active Line Modules
Table 5- 23
Technical data for Active Line Modules, 3 AC 500 ... 690 V, Part 1
Article number
Rated power
- At I
(50Hz 690V)
L DC
- At I
(50Hz 690V)
H DC
- At I
(50Hz 500V)
L DC
- At I
(50Hz 500V)
H DC
- At I
(60Hz 575V)
L DC
- At I
(60Hz 575V)
H DC
DC-link current
- Rated current I
N DC
- Base load current I
L DC
- Rated current I
H DC
- Maximum current I
max DC
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- DC-link voltage
Infeed/regenerative feedback current
- Rated current I
N E
- Maximum current I
2)
max E
Pulse frequency
Electronics current consumption (24 V DC)
Cooling method
Power loss, max.
3)
- At 50 Hz 690 V
- At 60 Hz 575 V
- Dissipated to the ambient air
Max. coolant temperature
- Without derating
- With derating
Rated flow rate
Pressure drop, typical
at the rated flow rate
4)
Liquid volume of integrated heat exchanger
DC-link capacitance
- Active Line Module
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
190
6SL3335–
kW
kW
kW
kW
HP
HP
A
A
A
A
1)
V
ACrms
Hz
V
DC
V
DC
A
A
kHz
A
kW
kW
kW
°C
°C
l/min
Pa
dm³
µF
dB(A)
mm²
mm²
mm²
7TG35–8AA3 7TG37-4AA3
630
800
620
705
447
560
450
510
675
900
506
600
644
823
627
800
573
732
966
1235
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
24 (20.4 ... 28.8)
575
735
862
1100
2.5
2.5
1.6
1.6
Liquid cooling with integrated aluminum heat exchanger
5.6
7.65
4.9
6.67
0.16
0.2
45
45
50
50
16
16
70000
70000
0.74
0.74
9670
10500
54
54
Flat connection for M12 screw
4 x 185
4 x 185
Busbar
Busbar
4 x 185
4 x 185
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
7TG38-1AA3
7TG41–0AA3
900
1100
670
1000
620
780
485
710
975
1250
765
1000
907
1147
883
1193
808
1022
1360
1722
47 ... 63Hz
1.5 x U
line
810
1025
1214
1537
2.5
2.5
1.6
1.6
8.5
10.9
7.4
9.53
0.22
0.53
45
45
50
50
16
27
70000
70000
0.74
1.56
10500
19330
54
56
4 x 185
Busbar
Busbar
Busbar
4 x 185
Busbar
Liquid-cooled chassis power units