Siemens Sinamics S120 Manual page 273

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Table 7- 21
Technical data of the dv/dt filter plus voltage peak limiter, 500 V ... 690 V 3 AC, Part 2
Article number
Suitable for Motor Module
Type rating of the Motor
Module
I
thmax
Degree of protection
dv/dt reactor
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- To the Motor Module
- Load
- PE
Max. permissible cable
length between dv/dt reactor
and motor
Dimensions
Width
Height
Depth
Weight, approx.
Voltage peak limiter
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- To the dv/dt reactor
- DC
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Two dv/dt reactors are required for these dv/dt filters. The technical data provided apply to one dv/dt reactor.
1)
Note
Cable lengths for versions with two dv/dt reactors
For versions with two dv/dt reactors, the cable lengths specified in the table do not change.
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3000-
2DH35-8AA0
6SL3325-
1TG34-7AAx
1TG35-8AAx
kW
450 / 560
A
575
IP00
kW
0.862
kW
0.902
kW
0.964
M12
M12
M6
m
mm
460
mm
385
mm
312
kg
172
kW
0.063
kW
0.059
kW
0.054
M8
M8
M8
mm
309
mm
1312.5
mm
400
kg
48
Motor-side power components
7.3 dv/dt filter plus Voltage Peak Limiter
2DH38-1AA0
2DH41-3AA0
1)
1TG37-4AAx
1TG41-0AAx
1TG38-0AAx
1TG41-3AAx
1TG38-1AAx
710 / 800 / 800
1000 / 1200
810
1270
IP00
IP00
0.828
0.865
0.867
0.904
0.927
0.966
2 x M12
2 x M12
2 x M12
2 x M12
M6
300 (shielded)
450 (unshielded)
445
385
312
160
0.106
0.15
0.1
0.14
0.091
0.128
M10
M10
M10
M10
M8
309
1312.5
1312.5
400
72
1)
M6
445
385
312
164
M8
309
400
72
273