Damage to motor in the event of incorrectly connected KTY temperature sensor
If a KTY temperature sensor is connected with incorrect polarity, it is not possible to detect
when the motor overheats. Overheating can cause damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130, PT100, PT1000 or PTC measuring sensor in the stator windings.
Note
Connection to terminal strip -X9
A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and
-X9:7.
4.3.6

X42 terminal strip

Table 4- 5
Max. connectable cross-section: 2.5 mm
Note
The terminal strip supplies power to the CU310 Control Unit via a cable harness supplied
with the device.
Note
Connection options of terminal strip X42
The terminal strip is not intended to supply other 24 VDC loads (for example, for supplying
other components on the plant/system side), as the voltage supply of the Control Interface
Module could also be overloaded and result in malfunctions.
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
Function
1
P24L
2
3
M
4
Technical data
Power supply for Control Unit, Sensor Module
and Terminal Module (18 ... 28.8 V)
maximum load current: 3 A
2