Safety Information - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Motor-side power components
7.1 Sine-wave filter
7.1.2

Safety information

Danger to life if the fundamental safety instructions and remaining risks are not carefully
observed
The non-observance of the fundamental safety instructions and residual risks stated in
Chapter 1 can result in accidents with severe injuries or death.
• Adhere to the fundamental safety instructions.
• When assessing the risk, take into account residual risks.
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel through
smoke development and fire. Furthermore, an increased number of failures and shorter
service life of the components can occur.
• Maintain 100 mm ventilation clearances above and to the side of the component.
Risk of burns resulting from high surface temperature of the sine-wave filter
The surface temperature of the sine-wave filters can exceed 80 °C. You can get seriously
burnt when touching the surface.
• Mount the sine-wave filter so that it cannot be touched. If this is not possible, attach a
NOTICE
Sine-wave filter damage due to interchanged connections
Interchanging the input and output connections will damage the sine-wave filter.
• Connect the incoming cable from the Power Modules or Motor Modules to 1U1, 1V1,
• Connect the outgoing cable to the load at 1U2, 1V2, 1W2.
NOTICE
Damage to the Motor Module by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use sine-wave filters that SIEMENS has released for SINAMICS.
244
WARNING
WARNING
CAUTION
clearly visible and understandable warning notice at hazardous positions.
1W1.
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7