Siemens Sinamics S120 Manual page 293

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Table 7- 31
Technical data of the dv/dt filter compact plus voltage peak limiter, 500 V ... 690 V 3 AC, Part 3
Article number
Suitable for Motor Module
(unit rating)
I
thmax
Degree of protection
Power loss
- At 50 Hz
- At 60 Hz
- At 150 Hz
Max. permissible cable
length between dv/dt filter
and motor
dv/dt reactor
Terminals
- 1U1/1V1/1W1
- 1U2/1V2/1W2
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Voltage peak limiter
Terminals
- DCPS/DCNS
- 1U2/1V2/1W2
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3000-
2DG38-1EA0
6SL3325-
1TG37-4AAx (710 kW)
1TG38-0AAx (800 kW)
1TG38-1AAx (800 kW)
A
810
IP00
kW
0.964
kW
0.998
kW
1.196
m
for 2 x M12 bolts
for 2 x M12 bolts
M6 screw
mm
430
mm
385
mm
323
kg
171.2
for M8 bolt
for M8 bolt
for M6 screw
mm
277
mm
360
mm
291
kg
18.8
Motor-side power components
7.4 dv/dt filter compact plus Voltage Peak Limiter
2DG41-3EA0
1TG41-0AAx (1000 kW)
1TG41-3AAx (1200 kW)
1270
IP00
1.050
1.104
1.319
100 (shielded)
150 (unshielded)
for 2 x M12 bolts
for 2 x M12 bolts
M6 screw
430
385
323
175.8
for M8 bolt
for M8 bolt
for M6 screw
277
360
291
19.2
293

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simanics s120

Table of Contents