Line Modules
5.3 Active Line Modules
Table 5- 22
Technical data for Active Line Modules, 3 AC 380 ... 480 V, Part 2
Article number
Rated power
- At I
(50Hz 400V)
L DC
- At I
(50Hz 400V)
H DC
- At I
(60Hz 460V)
L DC
- At I
(60Hz 460V)
H DC
DC-link current
- Rated current I
N DC
- Base load current I
L DC
- Rated current I
H DC
- Maximum current I
max DC
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- DC-link voltage
Infeed/regenerative feedback current
- Rated current I
N E
- Maximum current I
2)
max E
Pulse frequency
Electronics current consumption (24 V DC)
Cooling method
Power loss, max.
3)
- At 50 Hz 400 V
- At 60 Hz 460 V
- Dissipated to the ambient air
Max. coolant temperature
- Without derating
- With derating
Rated flow rate
Pressure drop, typical
at the rated flow rate
4)
Liquid volume of integrated heat exchanger
DC-link capacitance
- Active Line Module
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
Max. cable length
(total of all motor cables and DC link)
- Shielded
- Unshielded
188
6SL3335–
kW
kW
HP
HP
A
A
A
A
1)
V
ACrms
Hz
V
DC
V
DC
A
A
kHz
A
kW
kW
kW
° C
° C
l/min
Pa
dm³
µF
dB(A)
mm²
mm²
mm²
m
m
7TE41–4AA3
900
780
1250
1000
1573
1534
1401
2361
3 AC 380 -10% (-15% < 1 min) ... 3 AC 480 +10%
24 (20.4 ... 28.8)
1405
2107
2.5
1.6
Liquid cooling with integrated heat exchanger made of
Aluminum
10.2
11.19
0.62
45
50
27
70000
1.56
28800
54
Flat connection for M12 screw
Busbar
Busbar
Busbar
3900
5850
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
47 ... 63Hz
1.5 x U
line
Liquid-cooled chassis power units