Siemens Sinamics S120 Manual page 239

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Table 6- 17
Derating factor of the output current as a function of the pulse frequency for devices with a rated pulse fre-
quency of 2 kHz
Article No.
Type rating
6SL3325-...
[kW]
1TE32-1AA3
110
1TE32-6AA3
132
1TE33-1AA3
160
1TE35-0AA3
250
1TE41-4AS3
800
Table 6- 18
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency
of 1.25 kHz
Article No.
Type rating
6SL3325-...
[kW]
1TE36-1AA3
315
1TE37-5AA3
400
1TE38-4AA3
450
1TE41-0AA3
560
1TE41-2AA3
710
1TE41-4AA3
800
1TG31-0AA3
90
1TG31-5AA3
132
1TG32-2AA3
200
1TG33-3AA3
315
1TG34-7AA3
450
1TG35-8AA3
560
1TG37-4AA3
710
1TG38-0AA3
800
1TG38-1AA3
800
1TG41-0AA3
1000
1TG41-3AA3
1200
1TG41-6AA3
1500
Device 6SL3325-1TG38-0AA3 is optimized for a base pulse frequency of 1.25 kHz, for an increased pulse frequency,
1)
the derating factor is higher than for the device with article number 6SL3325-1TG38-1AA3.
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
Output current
at 2 kHz
[A]
Connection voltage DC 510 ... 720 V (line voltage 3 AC 380 ... 480 V)
210
260
310
490
1330
Output current
at 1.25 kHz
[A]
Connection voltage DC 510 ... 720 V (line voltage 3 AC 380 ... 480 V)
605
745
840
985
1260
1405
Connection voltage DC 675 ... 1035 V (line voltage 3 AC 500 ... 690 V)
100
150
215
330
465
575
735
810
1)
810
1025
1270
1560
Derating factor at the pulse frequency
2.5 kHz
4 kHz
95%
82%
95%
83%
97%
88%
94%
78%
88 %
55 %
Derating factor at the pulse frequency
2 kHz
2.5 kHz
83%
72%
83%
72%
87%
79%
92%
87%
92 %
87 %
97%
95%
92%
88%
90%
84%
92%
87%
89%
82%
92%
87%
91%
85%
84 %
74 %
83%
72%
97%
95%
91%
86%
87%
79%
87%
79%
Motor Modules
6.6 Technical specifications
5 kHz
7.5 kHz
74%
54%
74%
54%
78%
54%
71%
53%
--
--
4 kHz
5 kHz
64%
60%
64%
60%
64%
60%
70%
60%
70 %
60 %
74%
60 %
71%
60%
66%
55%
70%
60%
65%
55%
67%
55%
64%
50%
53 %
40 %
49%
35%
71%
55%
64%
50%
55%
40%
55%
40%
8 kHz
50%
50%
50%
50%
--
7.5 kHz
40%
40%
40%
50%
50%
50%
40%
35%
40%
40%
35%
35%
25 %
25%
35%
30%
25%
26%
239

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simanics s120

Table of Contents