D20E-C Module Control Outputs - GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Advertisement

CHAPTER 7: CONNECTING FIELD WIRING TO THE D20E MODULE

D20E-C module control outputs

D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
The D20E-C has 10 on-board relays that are factory configured into a variety of output
types; see Table 27 for connection details.
See Table 26 for termination block details.
The W1 to W12 jumpers are located on the D20E-K as shown in Figure 24.
Figure 24: D20E-C module - jumper locations
Table 27: D20E-C - summary of control types and jumper setting positions
Control Type
Trip/Close
Trip/Close supply TB2-2(+/‒) and TB2-51(‒/+)
LOCAL/REMOTE Switch supply: TB2-1(+/‒) and TB2-
51(‒/+)
DPST
Control Output supply TB2-1(+) and TB2-51(‒)
Form C
LOCAL/REMOTE Switch supply: TB2-1(+/‒) and
TB2-51(‒/+)
Raise/Lower
R/L supply TB2-2 (+/‒) and TB2-51 (‒/+)
LOCAL/REMOTE Switch supply: TB2-1(+/‒) and
TB2-51(‒/+)
Jumpers
W1 to W12
Jumper and Supply
W3-W9, W11
W1 and W2
W3-W9, W11
W1 and W2
W3-W9, W11
W10 and W12
W3-W9, W11
W1
W2
GE INFORMATION
Setting
99