Power source connection
84
Each D20E module requires 5W of power using an external 24/48 VDC power supply.
Figure 16 shows the location of the redundant power supply connections.
Figure 16: D20E redundant power supply connections
The wiring connected to terminal block TB1 must not have exposed accessible
conductors.
The wire and cable connected must have at least a +80
Ensure that the external power source is shut off before connecting or disconnecting
the power supply to the D20E Ethernet I/O Module. Use an approved external 20A
switch or circuit breaker that opens all conductors simultaneously. The switch or
circuit breaker must be suitably located, easily reached, and labeled appropriately.
Table 20: D20E-DC power and i/o supply connections
Power supply type
D20E External Power Supply connection
D20E-K Control Output External Supply
D20E-K (DB25) Interface
D20E-S Digital Input Wetting
External Supply
D20E-A Analog Input Loop
External Supply
D20E-C Digital Input Wetting External
Supply and
Control Output External Supply
The Control Output external supplies listed above must be connected in order to facilitate
the D20E-K (see section
Control output external supply
Local switch (see section
D20E-C module -Local/Remote switch
GE INFORMATION
CHAPTER 6: PRELIMINARY POWER UP AND TEST
Redundant power
supply connections
C temperature rating.
°
Description
DC Input 1+
DC Input 1-
1
2
TB1
3
4
DC Input 2+
DC Input 2-
TB2-54 (+/‒)
TB2-1 (‒/+)
TB2-3 (+/‒)
TB2-1 (‒/+)
TB2-65 (+/‒)
TB2-131 (‒/+)
TB2-49 (+)
TB2-99 (‒)
TB2-1 (+/‒) Digital Input (Control Output supply for DPST)
TB2-51 (‒/+) Digital Input (Control Output supply common
return)
TB2-2 (+/‒) Control Output (Trip/Close and Raise/Lower)
on page 90) and D20E-C Remote/
on page 100).