GE Multilin D20E Installation And Maintenance Manual page 117

Ethernet i/o module
Table of Contents

Advertisement

D20E Ethernet I/O Module
Appendix A: Standards & Protection
Compliance standards
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Standards & Protection
Compliance standards are listed for the following categories:
Table 40: Emission standards
Table 41: Immunity standards
Table 42: Safety publications
Table 43: Environmental standards
Table 44: Communication standards
Table 40: Emission standards
Standard Name
Description
1
ISM RF equipment – Electromagnetic
EN55011 (CISPR 11)
disturbance characteristics
1
To comply, all RS232 cables must be double shielded (that is, foil shield plus braid).
Table 41: Immunity standards
Standard Name
Description
IEC 61000-4-2
Electrostatic discharge (ESD) immunity
test
IEC 60255-22-2
®
IEEE
C37.90.3
IEC 61000-4-3
Radiated, radio-frequency
electromagnetic field immunity test
IEC 60255-22-3
IEEE C37.90.2 (10 V/m)
IEC 61000-4-4
Electrical fast transient/burst immunity
test
IEC 60255-22-4
IEEE C37.90.1
IEC 61000-4-5
Surge immunity test
on page 121
on page 121
on page 122
on page 122
on page 123
GE INFORMATION
Test Specification
Radiated Emissions 30 MHz to
1 GHz
Conducted Emissions 150 kHz to
30 MHz
Test Specification
8 kV contact
15 kV air discharge
80 MHz to 1.0 GHz, 10 V/m
1.4 GHz to 2.0 GHz, 3 V/m
2.0 GHz to 2.7 GHz, 1 V/m
±4.0 kV CM/TM
±2.0 kV / 4.0 kV TM/CM
121

Advertisement

Table of Contents
loading

Table of Contents