D20E Ethernet I/O Module
Chapter 7: Connecting Field Wiring
to the D20E Module
D20E-A analog inputs module
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Connecting Field Wiring to the D20E Module
This chapter describes the I/O connection for each type of D20E module:
D20E-A analog inputs module
D20E-K control outputs module
D20E-S digital inputs module
D20E-C combination inputs and outputs module
Field wiring is connected to the D20E modules at terminal block TB2.
The D20E-A supports up to 32 differential analog inputs. The field terminations for analog
inputs are provided by TB2-1 to TB2-48 and TB2-51 to TB2-98 (See Table 21 for details).
One shield termination is allocated for each input.
Table 21 lists the TB2 terminal block connection assignments for the D20E-A.
The wiring connected to terminal block TB2 must not have exposed accessible
conductors.
The wire and cable connected must have at least a +80
Table 21: D20E-A - analog input module terminal block assignments
TB2
Descriptions
1
Analog Input 1+
2
Shield/Screen Ground
3
Analog Input 2+
4
Analog Input 3+
5
Shield/Screen Ground
6
Analog Input 4+
7
Analog Input 5+
8
Shield/Screen Ground
9
Analog Input 6+
10
Analog Input 7+
on page 87
on page 89
on page 95
on page 97
C temperature rating.
°
TB2
Descriptions
51
Analog Input 1
52
Shield/Screen Ground
53
Analog Input 2
54
Analog Input 3
55
Shield/Screen Ground
56
Analog Input 4
57
Analog Input 5
58
Shield/Screen Ground
59
Analog Input 6
60
Analog Input 7