Control outputs
28
Control Output
• D20E-C
Configuration Options
8 Form C (NO and NC) outputs
6 Form C with 2 Form A supervision outputs
8 Trip/Close pairs (reserved for backward compatibility)
8 DPST (Double Pole Single Throw) outputs
8 Form C
4 Raise/Lower pairs
• D20E-K
32 Form C (NO and NC) outputs
32 Trip/Close pairs
32 DPST (Double Pole Single Throw) outputs
16 Raise/Lower pairs
Control Modes
• Direct Operate
• Select before Operate
• Single Point-of-Failure Protection excluding relay contacts
Local/remote Switch
Disable or Enable control outputs and control output supply
Contact Ratings
• 290 VDC maximum
• 8 A switching maximum (at 30 VDC)
• 4 A continuous maximum (Form C)
• 2 A continuous maximum (Trip/Close, Raise/Lower, DPST)
• 60 W Switching maximum (at 290 VDC)
Insulation/Isolation
2800 VDC
>100 MΩ
Programmable Output
Configurable:
Timers
• 20 to 100,000 ms
Programmable Pulse
Configurable:
Outputs
• Number of pulses: 1 to 20,000 (a configuration setting value of 0
specifies continuous pulses)
• On/Off durations: 20 to 100,000 ms
Local Indications
Red LED per output:
• D20E-K
• D20E-C: 1 to 8
Remote/Local: Red/Blue LEDs
Conducted Immunity
As per:
• IEEE C37.90.1
• IEC 61000-4-4
• IEC 61000-4-5
• IEC 61000-4-6
• IEC 61000-4-16
D20E-K (DB25) Interface • DB25(F) connectors
Note: Mating hood width <0.65"
• D20 KI interposer relay panel compatible
• 32 Trip/Close (30 T/C), 16 Raise Lower outputs
• External control supply input: 24/48 VDC nominal
• Dielectric insulation: 1400 VDC
• Conducted Immunity: IEEE C37.90.1, IEC 61000-4-4
• D20E-K (DB25) interface connects to WESTERM D20KI 517-0143 with
cable 977-0069
GE INFORMATION
:
:
:
1 to 32
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL