GE Multilin D20E Installation And Maintenance Manual page 70

Ethernet i/o module
Table of Contents

Advertisement

72
Setting
Descriptions
Number of
Specify the number of pulses to be sent. A
Pulses
value of 0 (zero) specifies continuous pulses.
Pulses are only supported on the Raise/Lower
boards.
Note: A pulse count on Trip/Close or Form C
boards prevents the controls from operating.
Pulse On
Specify the length of Pulse ON, in ms.
Duration
DNP3.0 controls overwrites this setting with the
ON time from the remote client.
Controls with an ON duration <20ms do not
operate. Controls received with an ON duration
of 0ms execute with the specified Pulse ON
Duration.
Pulse Off
Specify the length of Pulse OFF, in ms.
Duration
DNP3 controls overwrites this setting with the
OFF time from the remote client.
Controls received with an OFF duration <20ms
will execute with a default of 50ms.
Publisher settings
Reference
Specify a text string that combines the bay
Name
name, group name, and provider name from
the General tab.
Point
Specify the point description of the mapped
Description
digital output.
Value Type
Specify the date type the Publisher application
uses when reporting the Digital Output when
supported by the protocol.
Open Output
Specify the RTDB point associated with the
DO
digital output for a close operation. A custom
window allows you to associate the digital
output to any digital output, digital input or
analog input available in the D20E.
Close Output
Specify the RTDB point associated with the
DO
digital output for an open operation. A custom
window allows you to associate the digital
output to any digital output, digital input or
analog input available in the D20E.
Operation
Specify the control operation.
Method
The digital output options vary per protocol.
Ensure that the selected operation format
matches the control to be issued from the
remote Client.
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Range
1 to 20000 pulses
20 to 100000 ms
20 to 100000 ms
Single point
Double point
Trip/close an output in
the remote device
Regulating step
operation in the remote
device
Reset the remote device
Freeze the counters in
the remote device
Trip Only an output in the
remote device
Close Only an output in
the remote device
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Default
1 pulse
50 ms
50 ms