Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual page 479

Table of Contents

Advertisement

(b) Error clear
The following processing time is required to clear continuation errors stored in SD50 on the rising edge of
SM50 (Error reset).
CPU module
Q00UJCPU, Q00UCPU, Q01UCPU
Q02UCPU
Q03UD(E)CPU
Q04UD(E)HCPU, Q06UD(E)HCPU, Q10UD(E)HCPU, Q13UD(E)HCPU,
Q20UD(E)HCPU, Q26UD(E)HCPU, Q50UDEHCPU, Q100UDEHCPU
Q03UDVCPU, Q04UDVCPU, Q04UDPVCPU, Q06UDVCPU,
Q06UDPVCPU, Q13UDVCPU, Q13UDPVCPU,Q26UDVCPU,
Q26UDPVCPU
(c) Error clear by types
The following processing time is required to clear continuation errors by types.
CPU module
Q03UDVCPU, Q04UDVCPU, Q04UDPVCPU, Q06UDVCPU,
Q06UDPVCPU, Q13UDVCPU, Q13UDPVCPU, Q26UDVCPU,
Q26UDPVCPU
(6)
Device data latch processing time
When the latch range is set in the Device tab of the PLC parameter dialog box
the following tables is required. Each N1, N2, and N3 in the table indicates the following.
• N1: Number of devices specified to be latched (Count the latch range (1) and the latch range (2) as different
devices.)
• N2: Number of bit device points specified to be latched
• N3: Number of word device points specified to be latched
Processing time in END processing
When the error is cleared
(the one detected by the
annunciator)
0.185ms
0.180ms
0.068ms
0.065ms
0.03ms
Processing time in END processing
When the error is cleared
(the one detected by the
annunciator)
0.04ms
*1 *2 *3
, the processing time listed in
APPENDICES
When the error is cleared
0.180ms
0.175ms
0.062ms
0.062ms
0.026ms
When the error is cleared
0.036ms
477