(c) Using an external device in the MC protocol
Use MC protocol commands. For commands, refer to the following.
MELSEC Communication Protocol Reference Manual
• The PAUSE contact (SM204) turns on during END processing of the scan where the remote PAUSE
command is executed.
The CPU module executes one more scan until the END instruction after the scan where the PAUSE
contact turns on, and then changes its operating status to PAUSE. In the PAUSE status, the program
operations are stopped.
• Upon execution of the remote RUN command, the CPU module will restart the sequence program
operations from the step 0.
0
OFF
Remote PAUSE
command
OFF
Remote RUN
command
OFF
SM204
RUN/PAUSE
status
(3) Precautions
(a) When forcibly keeping output status (on or off)
To forcibly keep the output status (on or off) in the PAUSE status, provide an interlock with the PAUSE contact
(SM204).
M20
SM204
X0
M0
SM204
END
0
END
ON
ON
Turns on when the
PAUSE conditions
are established.
RUN
PAUSE status
The on/off status of Y70 is determined by the
Y70
on/off status of M20 in the PAUSE status.
Y71
Y71 turns off in the PAUSE status.
Y72
Y72 turns on in the PAUSE status.
0
END
0
ON
PAUSE
RUN
CHAPTER 3 FUNCTIONS
135