Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual page 134

Table of Contents

Advertisement

(3) Executing method
(a) Using a RUN contact
Set a RUN contact in the PLC system tab of the PLC parameter dialog box.
The settable device range is X0 to 1FFF.
The remote RUN/STOP operation can be performed by turning on/off the set RUN contact.
• When the RUN contact is turned off, the CPU module status changes to RUN.
• When the RUN contact is turned on, the CPU module status changes to STOP.
CPU module: RUN/STOP status
(b) Using a programming tool
Select [Online] [Remote Operation] "RUN" or "STOP".
(c) Using an external device in the MC protocol
Use MC protocol commands. For commands, refer to the following.
MELSEC Communication Protocol Reference Manual
External device
(d) With link dedicated instructions of the CC-Link IE module or MELSECNET/H module
The remote RUN/STOP operation by link dedicated instructions of the CC-Link IE module or MELSECNET/H
module can change the RUN/STOP status of the CPU module.
For details, refer to the following.
Manual for each network module
132
Step 0
OFF
RUN contact
RUN
Step 0
ON
Remote STOP
OFF
command
OFF
Remote RUN
command
RUN
RUN/STOP status
Step 0
END
ON
STOP
STOP status
END
STOP
STOP status
END
0
Step 0
END
0
ON