Encoder module
(option)
Terminal sizes
5k A UM
Connect the overall shield and the individual shields of the encoder
cable to the separate shield grounding point
connect the cable directly to the encoder
The unshielded cable ends must be as short as possible. The shield
ends which are fixed to the ground clamp must be not longer than 50
mm.
Fig. 6-16
Encoder module – Shield grounding point
A shield grounding point consists of a slotted mounting bracket
6-16: 3)
which has been mounted in the factory, and a ground clamp.
Depending on the layout of the swing frame, the shield grounding
points can be mounted at a different place than shown in
Three ground clamps of different sizes are supplied to accommodate
encoder cables of different diameters. The clamps are tied to each
mounting bracket.
SK 8
Fig. 6-17
Control cables – Shield grounding clamps
The terminals are suitable for wires with a maximum cross-section of 0.2
2
to 2.5 mm
.
3BHS221906 ZAB E01 Rev. D
Chapter 6 - Electrical installation
(Fig. 6-16:
(Fig. 6-16:
1).
1
2
3
SK 20
SK 14
2). Do not
(Fig.
Fig.
6-16.
6-19 (22)