Chapter 9 - CDP control panel
9.8.2

Remote control

9-20 (24)
In remote control mode, operational commands or reference values
usually come from a higher-level control system via fieldbus or remote I/O.
However, with the following parameter settings it is possible to start and
stop the drive, to set the motor's direction of rotation, and to enter
reference values from the CDP control panel.
11.01 EXT1 START/STOP/DIR = 10 (KEYPAD) or
12.03 EXT REF1 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 1 (EXT1)
11.02 EXT2 START/STOP/DIR 10 (KEYPAD) or
12.06 EXT REF2 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 2 (EXT2)
To enter remote control, press the LOC-REM key.
Full remote control from a higher-level control system is indicated by
a blank space.
Partial remote control (some commands enabled locally) is indicated
by the letter R.
3BHS221906 ZAB E01 Rev. D
1
600.0 rpm
ReadyRun
StateINU
MOTOR SP
0.00 rpm
POWER
0.0 kW
600.0 rpm
1 R
ReadyRun
StateINU
0.00 rpm
MOTOR SP
POWER
0.0 kW
ABB
0
0
5k A UM