Chapter 8 - Operation
8-10 (14)
The status line of the CDP control panel alternates between
Charging and AuxiliaryOn.
1 L ->
StateINU
MOTOR SP
POWER
When charging has been finished, the following takes place:
■
The MCB closes automatically.
■
The SUPPLY ON pushbutton lights up permanently.
.
1 L ->
StateINU
MOTOR SP
POWER
6
Enter the reference value.
For further information, see
1 L ->
StateINU
MOTOR SP
POWER
7
Start the motor.
When the motor has been magnetized, the motor speed ramps up to
the reference value.
While the motor is accelerating, the run status message on the
display blinks. When the motor speed has reached the reference
value, the run status message lights up permanently.
3BHS221906 ZAB E01 Rev. D
0.0 rpm
Charging
0.00 rpm
0.0 kW
0.0 rpm
0
ReadyRun
0.00 rpm
0.0 kW
9.9.2 Entering a reference
[600.0 rpm] 0
ReadyRun
0.00 rpm
0.0 kW
ABB
Charging
AuxiliaryOn
value.
5k A UM