Chapter 10 - Preventive and corrective maintenance
10.6.3

De-energizing the drive locally

Stopping the motor
10-20 (36)
NOTICE
Foreign matter and particularly metallic dust can cause failure and
damage when the drive is energized.
Ensure that foreign matter cannot enter the cabinet:
Close the doors and cover openings completely when work is
discontinued.
Retrieve any foreign matter which accidentally dropped into the
cabinet.
The following section describes how to de-energize the drive using the
local operator panel of the drive. If the drive is controlled from remote,
follow the established shutdown procedures.
1
Check that the CDP control panel is connected.
2
Enable the local control mode of the CDP control panel.
For further information, see
3
Stop the motor.
When the motor has reached zero speed, the display shows
ReadyRun:
1 L ->
StateINU
MOTOR SP
POWER
3BHS221906 ZAB E01 Rev. D
Chapter 9 - CDP control
600.0 rpm 0
ReadyRun
0.00 rpm
0.0 kW
ABB
panel.
5k A UM