Power Distribution Subrack - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Table 3-2 6 kVA UPS technical specifications
Item
Rated capacity
Number of phases
Input power factor
Output power factor
Rated input voltage
Input voltage range
Rated input frequency
Input frequency range
Output frequency range 50 Hz±0.5%
Peak efficiency
Dimensions (H x W x
D)
Weight

3.2.3 Power Distribution Subrack

Table 3-3 Technical specifications
Item
Maximum input current
Number of phases
Input frequency
Input voltage
Issue 02 (2020-12-25)
NO TE
● The RS485 port supports only the Modbus RTU protocol.
● a: The USB port supports the serial port communication protocol. The USB port can be
used to export logs and send serial port commissioning commands.
● b: The RS232 port supports the serial port communication protocol. The RS232 port can
be used to export logs, send serial port commissioning commands, and upgrade the UPS
main power program online.
Copyright © Huawei Technologies Co., Ltd.
Specifications
6 kVA
1
≥ 0.99
≥ 0.9
220 V AC/230 V AC/240 V AC
110–280 V AC; < 176 V AC: derated; 110 V AC: 50%
load
50 Hz/60 Hz
● 50 Hz: 46–54 Hz
● 60 Hz: 56–64 Hz
Normal mode: 93% (online mode)
Normal mode: 90%
131 mm x 438 mm x 480 mm
15 kg
Specifications
63 A
1
50 Hz/60 Hz
220 V
3 System Architecture
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c00

Table of Contents