Commissioning The Wlds900 Water Sensor - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Check Method
Set T/H sensor alarm
thresholds.
----End

5.3.8.3 Commissioning the WLDS900 Water Sensor

If a water sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the
WLDS900 water sensor, and the other end has been connected to the AI/DI_2 port
on the ECC800-Pro.
Context
Procedure
Step 1 Set water sensor parameters.
1.
2.
3.
4.
5.
Issue 02 (2020-12-25)
To use the AI/DI sensor, enable the corresponding AI/DI port and name the
sensor. The specific alarm then can be reported.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is
described.
NO TE
The default alarm severity of the AI/DI port is Minor. If you want to change the alarm
severity, see How Should I Configure Alarm Parameters.
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration tab page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_2 to Leak
and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_2
Port Settings.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensor n > Running Parameters and set
High temperature alarm threshold, Low
temperature alarm threshold, High humidity
alarm threshold, and Low humidity alarm
threshold as required.
NOTE
The default values of High temperature alarm
threshold, Low temperature alarm threshold, High
humidity alarm threshold, and Low humidity alarm
threshold are 35.0°C, 5.0°C, 85.0% RH, and 15.0%
RH respectively.