FusionModule500 Smart Mini Data Center
User Manual
Pipe Length
Lay out pipes based on site requirements and the following principles:
● The length of a pipe should be as short as possible. The recommended length is
● Minimize the height difference between the indoor and outdoor units.
● Minimize the number of bends for pipes.
● The total length of the pipe connecting the indoor and outdoor units equals
Table 4-9 Equivalent length of the straight pipe (unit: mm)
Equivalent Length of Components
Copper Pipe
Diameter
15.88
12.7
9.52
6
If the pipe between the indoor unit and outdoor unit is longer than 10 m, increase
the pipe diameter to reduce system resistance. The following table lists the
recommended pipe dimensions.
Table 4-10 Pipe dimensions
Pipe Length
10 m
20 m
30 m
40 m
50 m
60 m
Issue 02 (2020-12-25)
NO TICE
within 10 m. Avoid unnecessary turnings, lifting, and falling.
the equivalent length of the straight pipe plus the length of the one-way
straight pipe connecting the indoor and outdoor units.
Equivalent Length
45-degree Bend
150
140
100
60
Copyright © Huawei Technologies Co., Ltd.
90-degree Bend
250
250
200
120
Gas Pipe
9.52
12.7
12.7
12.7
12.7
12.7
4 Installation Guide
180-degree Bend
500
500
340
240
Liquid Pipe
6
9.52
9.52
9.52
9.52
9.52
84